TESTING OF EQUIPMENTS

TESTING OF ELECTRICAL EQUIPMENT'S  and TYPES OF TESTING
         All the electrical equipment's like generators,power transformers, circuit breakers, isolators, earth switches, current transformers, voltage transformers,panels,relays,bus bars,cables (HV,LV),all types motors etc....are made at factory by customer interest.All are tested at factory before delivering to the customer this test we call as FACTORY TEST,but these heavy machines travels thousands of kilometers as to reach the site which may be remote areas or hill areas.
                    After delivering the site they are installed at respective places by using heavy hydraulic machines or labour. So there may be chance of damage in this process.so it is necessary to check once again before operating the machine.this will come under pre commissioning activities. We call it as ROUTINE TEST OR FIELD TEST OR PRE COMMISSIONING TEST.

Amount of megger voltage that should apply while doing megger test.
  vlotage rating of device     -  amount of megger voltage that shoulld apply
                 110v                 -     100v dc
  230v        -  250v dc
  415v        -  500v dc
  11kv        -  2500v dc
  25kv        -  2500v dc
  33kv        -  2500v dc
  66kv        -  2500v dc or 5000v dc
  132kv       -  5000v dc
  220kv       -  5000v dc
  400kv       -  5000v dc
  765kv       -  5000v dc or 10000v dc

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

CAPACITIVE VOLTAGE TRANSFORMER

POWER TRANSFORMER

ISOLATOR & EARTH SWITCH

BREAKER

WAVE TRAP

LIGHTNING ARRESTOR

POWER CABLE

BUS BAR

GENERATOR

MOTOR